Mitsubishi Electric
Mitsubishi Electric Error Code Search

Mitsubishi Electric

Mitsubishi Electric Error code search

Error code search offers information on the cause of the malfunction and the status of your air conditioner by entering the error code.

Disclaimers

  1. This page provides a simple explanation concerning content relating to error codes and their possible causes. Please note that the content may slightly differ depending on models.
  2. 212 HVAC assumes no responsibility for any accidents or troubles caused in the disassembly or repair of equipment performed according to information on this page.

Caution

If molded case circuit breakers or earth leakage circuit breakers have tripped, do not reset the breaker immediately without first checking for any problems with insulation of equipment.

Resetting breakers without a check of insulation may cause damage to equipment.

Mitsubishi air conditioning error codes

CODE: P1

RESULT: Intake sensor error.

CODE: P2 – P9

RESULT: Pipe (Liquid or 2-phase pipe) sensor error.

CODE: E6 – E7

RESULT: Indoor/outdoor unit communication error.

CODE: P4

RESULT: Drain sensor error.

CODE: P5

RESULT: Drain pump error.

CODE: PA

RESULT: Forced compressor error.

CODE: P6

RESULT: Freezing/Overheating safeguard operation.

CODE: EE

RESULT: Communication error between indoor and outdoor units.

CODE: P8

RESULT: Pipe temperature error.

CODE: E4

RESULT: Remote controller signal receiving error.

CODE: Fb

RESULT: Indoor unit control system error (memory error, etc.).

CODE: E0 – E3

RESULT: Remote controller transmission error.

CODE: E1 – E2

RESULT: Remote controller control board error.

CODE: E9

RESULT: Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit).

CODE: UP

RESULT: Compressor overcurrent interruption.

CODE: U3 – U4

RESULT: Open/short of outdoor unit thermistors.

CODE: UF

RESULT: Compressor overcurrent interruption (When compressor locked).

CODE: PA

RESULT: Forced compressor error.

CODE: U2

RESULT: Abnormal high discharging temperature/49C worked/insufficient refrigerant.

CODE: U1 – Ud

RESULT: Abnormal high pressure (63H worked)/Overheating safeguard operation.

CODE: U5

RESULT: Abnormal temperature of heat sink.

CODE: U8

RESULT: Outdoor unit fan safeguard stop.

CODE: U6

RESULT: Compressor overcurrent interruption/Abnormal of power module.

CODE: U7

RESULT: Abnormality of super heat due to low discharge temperature.

CODE: U9 – UH

RESULT: Abnormality such as over-voltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error.

Mr.Slim A-control error code list

Display of remote controller

CODE: EA

RESULT: Error detail Mis-wiring of indoor/outdoor unit. exceed the number of indoor unit connection. Inspected unit Outdoor.

CODE: Eb

RESULT: Error detail Mis-wiring of indoor/outdoor unit. (mis-wiring disconnection) Inspected unit Outdoor.

CODE: EC

RESULT: Error detail Start-up time over. Inspected unit Outdoor.

CODE: E6

RESULT: Error detail Indoor/outdoor unit transmission error (signal receiving error). Inspected unit Indoor.

CODE: E7

RESULT: Error detail Indoor/outdoor unit transmission error (transmitting error). Inspected unit Indoor.

CODE: E8

RESULT: Error detail Indoor/outdoor unit transmission error (signal receiving error). Inspected unit Outdoor.

CODE: E9

RESULT: Error detail Indoor/outdoor unit transmission error (transmitting error). Inspected unit Outdoor.

CODE: E0

RESULT: Error detail Remote control transmission error (signal receiving error). Inspected unit Remote control.

CODE: E3

RESULT: Error detail Remote control transmission error (transmitting error). Inspected unit Remote control.

CODE: E4

RESULT: Error detail Remote control transmission error (signal receiving error). Inspected unit Indoor.

CODE: E5

RESULT: Error detail Remote control transmission error (transmitting error). Inspected unit Indoor.

CODE: EF

RESULT: Error detail M-NET transmission error. Inspected unit Indoor and outdoor.

CODE: Ed

RESULT: Error detail Serial transmission error. Inspected unit Outdoor.

CODE: P1

RESULT: Error detail Abnormality of room temperature thermistor (TH1). Inspected unit Indoor.

CODE: P2

RESULT: Error detail Abnormality of pipe temperature thermistor/liquid (TH2). Inspected unit Indoor.

CODE: P4

RESULT: Error detail Abnomarlity of drain sensor (DS). Inspected unit Indoor.

CODE: P5

RESULT: Error detail Malfunction of drain-up machine. Inspected unit Indoor.

CODE: P6

RESULT: Error detail Freezing/overheating protection detect. Inspected unit Indoor.

CODE: P8

RESULT: Error detail Abnormality of pipe temperature. Inspected unit Indoor.

CODE: P9

RESULT: Error detail A-normality of pipe temperature thermistor/condenser/evaporator (TH5). Inspected unit Indoor.

CODE: F1

RESULT: Error detail Reverse phase detection.

CODE: F2

RESULT: Error detail L3 open phase detection.

CODE: F3

RESULT: Error detail 63L connector open.

CODE: F4

RESULT: Error detail 49C connector open.

CODE: F9

RESULT: Error detail Connector 2 or more open.

CODE: FA

RESULT: Error detail L2-phased open phase or 51CM connector open.

CODE: F7

RESULT: Error detail Reverse phase detection circuit (p.c.board) fault.

CODE: F8

RESULT: Error detail Input circuit fault.

CODE: U2

RESULT: Error detail Abnormal high discharging temperature.

CODE: U2

RESULT: Error detail Inner thermostat (49C) operation.

CODE: U1

RESULT: Error detail Abnormal high pressure (high pressure switch 63H worked).

CODE: U1

RESULT: Error detail Direct cut operation.

CODE: UE

RESULT: Error detail High pressure error (ball valve closed).

CODE: UL

RESULT: Error detail Over heat protection.

CODE: Ud

RESULT: Error detail Over heat protection.

CODE: U6

RESULT: Error detail Compressor over current (overload) cut off.

CODE: UA

RESULT: Error detail Compressor over current (terminal relay operation).

CODE: UF

RESULT: Error detail Compressor over current (start-up locked) cut off.

CODE: UF

RESULT: Error detail Compressor over current (operating locked) cut off.

CODE: UH

RESULT: Error detail Current sensor error.

CODE: U3

RESULT: Error detail Discharge thermistor short/open.

CODE: U4

RESULT: Error detail Outdoor thermistor short/open.

Mr.Slim K-control Display of remote controller.

CODE: LED E0

RESULT: Diagnosis of malfunction Transmitting/receiving signal error. Inspected unit Indoor.

CODE: LED P1

RESULT: Diagnosis of malfunction Intake air sensor abnormal. Inspected unit Indoor.

CODE: LED P2

RESULT: Diagnosis of malfunction Pipe sensor abnormal. Inspected unit Indoor.

CODE: LED P4

RESULT: Diagnosis of malfunction Drain sensor abnormal. Inspected unit Indoor.

CODE: LED P5

RESULT: Diagnosis of malfunction Malfunctioning of the drain overflow protecting mechanism. Inspected unit Indoor.

CODE: LED P6

RESULT: Diagnosis of malfunction Abnormality of the coil frost/overheating protection mode. Inspected unit Indoor.

CODE: LED P3

RESULT: Diagnosis of malfunction System error (transmitting/receiving signal). Inspected unit Indoor.

CODE: LED P7

RESULT: Diagnosis of malfunction System error (address). Inspected unit Indoor.

CODE: LED E8

RESULT: Diagnosis of malfunction Outdoor unit malfunction. Inspected unit Outdoor.

Mr.Slim K-control Outdoor unit

LED ON = Operation status

LED Flash = Check code display

CODE: LED LD1

RESULT: LED ON Compressor directive, LED Flash Reverse phase detect.

CODE: LED LD2

RESULT: LED ON Heating directive, LED Flash Open phase detect.

CODE: LED LD3

RESULT: LED ON During 63H1 operation, LED Flash Pipe sensor short/open.

CODE: LED LD4

RESULT: LED ON Compressor ON, LED Flash High pressure switch (63H2) operation.

CODE: LED LD5

RESULT: LED ON Outdoor fan ON, LED Flash Over current relay (51CM) operation.

CODE: LED LD6

RESULT: LED ON 4-way valve ON, LED Flash Thermal switch (26C) operation.

CODE: LED LD7

RESULT: LED ON Bypass valve ON, LED Flash Thermistor (TH3) overheat protection.

CODE: LED LD8

RESULT: LED ON Crankcase heater ON, LED Flash Detective input.

Mitsubishi Mr. Slim Error Codes – Membrane type remote controllers

Check codeDiagnosis of malfunctionCauseCheck points
EOSignal transmitting/receiving error (Indoor controller does not respond to remote controller signal)During individual unit control 1) Bad contact of transmission wire. 2) Signal transmitting/receiving circuit is abnormal.1) Check the transmission wire. 2) Check with another remote controller. If “EO” is still indicated, replace the indoor controller board. If other check code appears, replace the original remote controller.
P1Abnormality of room temperature thermistor (RT1)1) Bad contact of thermistor 2) Damaged thermistor1) Check the thermistor. 2) Measure the resistance of the thermistor. Normal resistance should be as follows. 32°F ····15kΩ 86°F ·····4.3kΩ 50°F ·····9.6kΩ 104°F ····3.0kΩ 68°F ·····6.3kΩ If the resistance is normal, replace the indoor controller board.
P2Abnormality of indoor coil thermistor (RT2)1) Bad contact of thermistor 2) Damaged thermistor1) Check the thermistor. 2) Measure the resistance of the thermistor. Normal resistance should be as follows. 32°F ····15kΩ 86°F ·····4.3kΩ 50°F ·····9.6kΩ 104°F ····3.0kΩ 68°F ·····6.3kΩ If the resistance is normal, replace the indoor controller board.
P3Signal transmission error (Remote controller does not respond to indoor controller signal)1) Bad contact of transmission wire. 2) Signal transmitting/receiving circuit is abnormal. 3) Wrong operation due to noise wave emitted by other appliances.1) Check the transmission wire. 2) Check with another remote controller. If “P3” is still indicated, replace the indoor board. If other check code appears, replace the original remote controller. 3) Short-circuit between 1 and ➁ of CN40 and attach CN40 to the following units: • Second unit in twin control • Second and third units in triple control • Sub units in group control
P4Abnormality of drain sensor1) Bad contact of transmission wire 2) Damaged thermistor1) Check the connector. 2) Measure the resistance of the thermistor ➃ – ➄. As for the normal resistance, refer to the case of P1. If the resistance is normal, replace the indoor controller board.
P5Malfunction of drain pump1) Malfunction of drain pump 2) Damaged drain sensor1) Check the drain pump. 2) Check the drain sensor. • Check the drain sensor heater. Normal resistance should be 82Ω. If the resistance is normal, replace the indoor controller board.
P6Coil frost protection is working.1) Short cycle of air cycle 2) Dirty air filter 3) Damaged fan 4) Abnormal refrigerant1) Clear obstructions from the air cycle. 2) Clean the air filter. 3) Check the fan. 4) Check the refrigerant temperature.
P7System error1) Wrong address-setting 2) Signal transmitting/receiving circuit of remote controller is abnormal. 3) Wrong SW6-setting1) Check the address-setting. 2) Check with another remote controller. If check code other than “P7” appears, replace the original remote controller. 3) Check SW6 setting.
P8Abnormality in outdoor unit1) Wrong wiring of indoor/outdoor connecting wire 2) Reversed phase 3) Protection device is working 4) Damaged outdoor coil thermistor1) Check the indoor/outdoor connecting wire. 2) Change the connection of electric wiring. 3) Check the protection device. 4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the outdoor controller board.